1. Check if the air source has air
2. Is the pressure detected by the pressure solenoid valve adjusted high
3. Is there a disconnection in the connecting line
4. The air pressure solenoid valve is broken
When there is a lack of air pressure, first check the pressure gauge to see if it is really a lack of air pressure. If it is really a lack of air pressure or a lack of air, check the air source.
If there is gas and an alarm is triggered, you can check if the pressure solenoid valve has set the pressure too high. Generally, it is enough to set it to 4MPA, but if it is too high, it can be reduced to 4MPA.
If the air pressure solenoid valve is not set too high, you can short circuit the signals X21 and+24V connected to the air pressure solenoid valve to see the diagnostic input signal in the system (FANUC system is the "signal" X3.0 in "PMC maintenance").
The new generation system is equipped with a diagnostic signal I016. Is there a signal change? If there is a signal change, it may be a problem with the air pressure solenoid valve. You can try replacing it with a new one.
·The processing center processing center processing and changing knives ·Non-standard precision hardware processing production process? ·How to choose the original position of injection molding mold custom processing workpiece · CNC Machining Machining, which is effective to reduce production costs ·Explanation of operating requirements for high-speed machining centers of gantry machining centers ·Explain the benchmark selection of processing and positioning of the processing center? ·The key to the improvement of high -speed processing center performance ·How to maintain the electrical system of CNC drilling machines in CNC machining centers CNC drilling ·CNC processing comparison of the advantages of 3D printing ·Reasons and solutions for unqualified zinc alloy pressure castings